Cooler-CW ( Pompa panas sumber air komersial untuk pendinginan & pemanasan) |
|
|
|
|
|
|
|
|
|
|
|
CL-CW-1609 |
|
|
|
CL11s-CW5 |
CL17s-CW5 |
CL11-CW5 |
CL17-CW5 |
CL24-CW5 |
CL34-CW10 |
CL48-CW10 |
CL68-CW20 |
CL80-CW20 |
CL120-CW20 |
CL160-CW20 |
Lubang terbuka bawah air |
Kapasitas pendinginan tetapan |
KW |
11 |
17 |
11 |
17 |
24 |
34 |
48 |
68 |
80 |
120 |
160 |
Daya input tetapan untuk pendinginan |
KW |
2.15 |
3.34 |
2.11 |
3.20 |
4.72 |
6.53 |
9.18 |
13.18 |
15.72 |
23.35 |
31.56 |
Arus input tetapan untuk pendinginan |
A |
9.55 |
14.84 |
3.98 |
6.04 |
8.91 |
12.33 |
17.35 |
24.91 |
29.71 |
44.12 |
59.64 |
Koefisien kinerja pendinginan (cooling performance coefficient -) |
/ |
5.12 |
5.09 |
5.22 |
5.32 |
5.09 |
5.21 |
5.23 |
5.16 |
5.09 |
5.14 |
5.07 |
Kapasitas pemanasan tetapan |
KW |
9.5 |
16 |
9.5 |
16 |
22 |
32 |
45 |
65 |
75 |
115 |
150 |
Daya input tetapan untuk pemanasan |
KW |
2.59 |
4.38 |
2.59 |
4.31 |
6.09 |
8.86 |
12.33 |
18.01 |
21.01 |
32.39 |
41.78 |
Arus input tetapan untuk pemanasan |
A |
12.33 |
20.87 |
4.89 |
8.15 |
11.52 |
16.75 |
23.30 |
34.03 |
39.71 |
61.23 |
78.97 |
Koefisien kinerja pemanasan (pemanasan, coefficient performance coefficient) |
/ |
3.67 |
3.65 |
3.67 |
3.71 |
3.61 |
3.61 |
3.65 |
3.61 |
3.57 |
3.55 |
3.59 |
Aliran air heat exchanger sisi aplikasi |
M3/j |
1.89 |
2.92 |
1.89 |
2.92 |
4.13 |
5.85 |
8.26 |
11.70 |
13.76 |
20.64 |
27.52 |
Aliran air heat exchanger sisi sumber panas |
M3/j |
1.03 |
1.59 |
1.03 |
1.59 |
2.25 |
3.19 |
4.50 |
6.38 |
7.51 |
11.26 |
15.01 |
Loop tertutup sumber ground |
Kapasitas pendinginan tetapan |
KW |
10 |
16 |
10 |
16 |
22 |
32 |
46 |
64 |
76 |
114 |
150 |
Daya input tetapan untuk pendinginan |
KW |
1.96 |
3.17 |
1.95 |
3.13 |
4.38 |
6.17 |
8.83 |
12.48 |
14.90 |
22.27 |
29.64 |
Arus input tetapan untuk pendinginan |
A |
8.70 |
14.11 |
3.68 |
5.91 |
8.28 |
11.65 |
16.69 |
23.58 |
28.16 |
42.08 |
56.03 |
Koefisien kinerja pendinginan (cooling performance coefficient -) |
/ |
5.11 |
5.04 |
5.13 |
5.12 |
5.02 |
5.19 |
5.21 |
5.13 |
5.10 |
5.12 |
5.06 |
Kapasitas pemanasan tetapan |
KW |
8 |
12 |
8 |
12 |
16 |
24 |
33 |
48 |
57 |
86 |
115 |
Daya input tetapan untuk pemanasan |
KW |
3.07 |
4.43 |
3.04 |
4.58 |
5.99 |
9.20 |
12.60 |
18.39 |
22.01 |
32.95 |
43.73 |
Arus input tetapan untuk pemanasan |
A |
13.27 |
19.17 |
5.66 |
8.52 |
11.15 |
17.10 |
23.43 |
34.21 |
40.93 |
61.29 |
81.33 |
Koefisien kinerja pemanasan (pemanasan, coefficient performance coefficient) |
/ |
2.61 |
2.71 |
2.63 |
2.62 |
2.67 |
2.61 |
2.62 |
2.61 |
2.59 |
2.61 |
2.63 |
Aliran air heat exchanger sisi aplikasi |
M3/j |
1.38 |
2.06 |
1.38 |
2.06 |
2.75 |
4.13 |
5.68 |
8.26 |
9.80 |
14.79 |
19.78 |
Aliran air heat exchanger sisi sumber panas |
M3/j |
1.72 |
2.58 |
1.72 |
2.58 |
3.44 |
5.16 |
7.10 |
10.32 |
12.26 |
18.49 |
24.73 |
Catu daya |
1N 220V/50Hz ( catu daya khusus untuk opsi) |
3N 380V/50Hz( Catu daya khusus untuk opsi) |
Kompresor |
Tipe |
Jenis gulir spesialis |
Kuantitas |
PC |
1 |
1 |
1 |
1 |
1 |
2 |
2 |
2 |
2 |
3 |
4 |
Heat exchanger sisi sumber panas |
Tipe |
Penukar panas Shell & coil (tabung) |
Ukuran koneksi |
DN |
DN20 |
DN25 |
DN25 |
DN25 |
DN25 |
DN32 |
DN32 |
DN50 |
DN65 |
DN65 |
DN80 |
Heat exchanger sisi aplikasi |
Tipe |
Penukar panas Shell & coil (tabung) |
Ukuran koneksi |
DN |
DN20 |
DN25 |
DN25 |
DN25 |
DN25 |
DN32 |
DN32 |
DN50 |
DN65 |
DN65 |
DN80 |
Perlindungan |
1. Perlindungan tekanan tinggi dan rendah, 2 . Perlindungan anti-beku, 3. Perlindungan temperatur tinggi, 4 . Perlindungan kelebihan beban, 5. Membalik proteksi fase, kurangnya perlindungan fase, dll. |
Refrigerant |
Tipe |
R410A |
Kuantitas |
KG |
2.6 |
3.3 |
2.6 |
3.3 |
4.2 |
3.3x2 |
4,2x2 |
6.6x2 |
7,6x2 |
7,6x3 |
7,6x4 |
Dimensi |
mm |
790x415x590 |
790x710x950 |
2000x1000x1600 |
Dimensi paket kayu (L*W*H) |
mm |
836x461x752 |
836x756x1112 |
2056x1056x1768 |
Berat bersih |
KG |
68 |
95 |
65 |
95 |
135 |
195 |
320 |
795 |
885 |
1180 |
1210 |
Bobot kotor |
KG |
78 |
105 |
75 |
105 |
145 |
215 |
340 |
830 |
920 |
1215 |
1245 |
Noise (kebisingan) |
DB(A) |
≤53 |
≤55 |
≤55 |
≤55 |
≤58 |
≤58 |
≤62 |
≤65 |
≤70 |
≤75 |
≤75 |
Catatan: |
1. Kondisi standar pendinginan tipe loop terbuka di bawah tanah: Temperatur input/output air di sisi aplikasi 12/7; input air sisi sumber/ suhu output 18C/29. Kondisi standar pemanasan tipe lingkaran terbuka air bawah tanah: Temperatur input/output air di sisi aplikasi 40/45; input air di sisi sumber/ suhu output 15C/A. |
2 . Kondisi standar pendinginan tipe loop tertutup di sumber tanah: Temperatur input/output air di sisi aplikasi 12/7; input air di sisi sumber, suhu output 25/30 Temperatur standar pemanasan tipe lingkar tertutup di sumber : Input air sisi pemasangan/ suhu output 40 C/45 ; input air sisi sumber 5celcius/suhu output 5celcius/A. |
3. "-a " berarti aliran air dalam kondisi standar pendinginan. |
Parameter di atas mungkin memiliki beberapa perbedaan dari produk akhir karena produk yang diperbarui, jadi informasi di atas bukanlah ketentuan kontrak bisnis. Harap lihat informasi yang dapat dirayapi produk akhir, atau lihat kami untuk informasi apa pun. Perusahaan kita terus berhak untuk menerjemahkan. |