Phase: | Three Phase |
---|---|
Type: | On-line |
Protection: | Short Circuit |
Application: | Communication |
Classification: | Lighting/Power |
Standby Time: | Standard Machine |
Pemasok dengan izin usaha terverifikasi
Spesifikasi Teknis Galaxy VX | UPS 500 KW HINGGA 1500 KW |
Topologi | Versi korelatif ganda pada baris dengan Mode eConversion (Konversi e) |
Nominsl Power (KVA | 500-1250 kW(kabinet input/output 1250 kW) 500-1500 kW(kabinet input/output 1500 kW) |
Peringkat Daya Teknis | 500 kW,625 kW,750 kW,800 KW,1000 KW 1100 kW,1250 kW,1500 kW |
Kemampuan paralel | Hingga 4 unit (N+1) |
Input (masukan) | |
Jenis Rnctifior | Rectifier aktif GBT |
Tegangan Input Nominal | 380V/400V/415V/440V/480V 3-Kabel (3PH+PE) or4Kabel(3PH+PE+N) (600 V dengan transformer eksternal opsional) |
NLetakkan Kisaran Tegangan | +20%/-15% |
NLetakkan Koneksi | Umpan tunggal atau ganda |
NLetakkan Frekuensi | 60 atau 50 Hz nominal (40-70 Hz) |
NPed Total Harmonic (Harmonis Total) saat ini Distorsi (THDI) |
<3% @100%muat |
NLetakkan faktor Daya | >0.99 |
Berjalan-jalan | 0 hingga 300s (dapat dikonfigurasi) |
Hubung-singkat tahan lama Peringkat |
100 KA |
Output | |
Tipe Inverter | 4 Level IGBT,efisiensi tinggi,tidak dapat ditransformer |
Tegangan Output Nominal | 380V/400V/415V/440V/480 V 3-Kabel (3PH+PE) or4Kabel (3PH+PE+N) (600 V dengan transformer eksternal opsional |
Faktor Daya Beban | 0.7 mengarah ke 0.5 akan tertinggal tanpa penurunan daya UPS |
Regatio | +/-1% |
Ragulasi Frekuensi | 50/60Hz +/-0.1% (Free Running |
Beban lebih di Norma Pengoperasian (di 40) |
Kontinu hingga 110%10 menit hingga 125% 1 menit hingga 150% |
Pintasan beban berlebih di Pintasan Pengoperasian (pada 40 derajat C) |
Terus menerus hingga 110%(380V/400V/ 415V/440V) Terus menerus hingga 125%(480 V) 1 menit hingga 150% (semua tegangan) |
Distorsi Tegangan Output (THDU) |
<2%at 100%beban linear; <3%pada beban 100%non linear |
Faktor Daya Output | 1.0 KVA =kW |
Detail Eficy | |
Mode konversi ganda | Hingga 96.5% |
Mode eConversion (Konversi e) | Hingga 99% |
Parameter penyimpanan energi | |
Tipe | Litium-ion, VRLA, Panggilan basah,Flywheel |
Tegangan Bus Nominal DC | 480 VDC |
String baterai umum | ( Saja |
Spesifikasi Teknis Galaxy VX | UPS 500 KW HINGGA 1500 KW |
Komunikasi | |
Grafis multibahasa 1Tampilan CD |
Ya |
Kompatibilitas dengan Kartu komunikasi |
AP9630 |
Detail Komunikasi | Modbus TCAGIP SNMP email Modbus RS-485 (opsional) |
Dimensi mekanis | |
Kabinet VO 1250 kW (H xWx D) | |
500 kW | 77,6x94,4x35.4in(1970x2400x900 mm) |
625/750 kW | 77,6x118,1x35,4in(1970x3000x900 mm) |
800/1000 kW | 77,6x141,6x35,4in(1970x3600x900 mm |
1100/1250 kW | 77,6x165,2x35.4in(1970x4200x900 mm) |
1250 kW N+1 | 77,6x188,8x35.4in(1970x4800x900 mm) |
Kabinet VO 1500 kW (H xWx D) | |
500kW | 77,6x126x35,4in(1970x3200x 900 mm |
750KW | 77,6x149,6x35,4in(1970x3800x 900 mm |
1000 kW | 77,6x173,2x35.4in(1970x4400x900 mm) |
1250 kW | 77,6x196,9x35.4in(1970x5000x900 mm) |
1500 kW | 77,6x220,5x35.4in(1970x5600x900 mm |
1500 kW N+1 | 77,6x245,1x35,4 in(1970x6200x900 mm |
Standar dan persetujuan | |
Kinerja dan Keselamatan | UL 17785th edisi, cUL CE, IEC 62040-1 EC 62040-3 (VFI-SS-111) |
Emisi EMC | FCC 47 Part 15 EC 62040-2 |
Seismic | OSHPD BC 2012 |
Lonjakan | ANSI 62.4/B3 |
P lewel (Perlindungan Susupan) | IP20 |
Lingkungan | |
Suhu Pengoperasian | 0-40 32-104 ( F) tanpa penurunan daya |
Kelembapan | 0-95%nonfonsing |
Ketinggian/Ketinggian | 1000 m(3333 ft)100%beban tanpa penurunan daya |
Fitur standar | |
Pengisi Daya lembut Start, Walk-in untuk Kompatibilitas dengan |
Ya,Adaptiative,bisa dikonfigurasi 1 menjadi 300s |
Fungsi Start dingin (Mulai dingin) (START tanpa listrik) |
Ya |
Emergency Stop (EPO) | Tidak |
Konverter Frekuensi | Ya |
Perlindungan Cadangan | Ya |
Uji Daya Pintar (spot) | Ya |