Aplikasi: | Daya |
---|---|
Fase: | Tiga |
Core: | Trafo tipe inti |
Metode Pendinginan: | Transformer Tipe terendam Oli |
Tipe kumparan: | Transformer multi-kumparan |
Sertifikasi: | ISO9001-2000, ISO9001 |
Pemasok dengan izin usaha terverifikasi
|
K. DAYA 400/200kV |
SATUAN |
DATA |
|
Diperlukan |
Ditawarkan |
|||
1 |
TRANSFORMER DAYA |
|
|
|
|
|
|
|
|
1.1 |
Produsen & tempat |
|
|
HEMG |
1.2 |
Ketik penetapan |
|
|
FSZ-200000/400 |
1.3 |
Tipe |
|
|
|
|
Transformer Otomatis tiga fase, tipe inti terendam oli dengan kumparan tertier |
|
|
Ya |
|
|
|
|
|
1.4 |
Standar |
|
|
IEC 60076, 60137, 60214 |
|
|
|
|
|
1.5 |
Ketinggian |
m |
|
216 |
|
|
|
|
|
1.6 |
Suhu sekitar |
|
|
|
|
- Maksimum |
|
|
40 |
|
- Rata-rata tahunan |
|
|
30 |
|
|
|
|
|
1.7 |
Pemasangan |
|
|
Luar ruang |
|
|
|
|
|
1.8 |
Rasio tegangan tetapan |
KV |
|
400 |
|
220 |
|||
|
11 |
|||
1.9 |
Frekuensi tetapan |
Hz |
|
50 |
|
|
|
|
|
1.1 |
Kelompok vektor (koneksi kelompok 3 fase) |
|
|
YNa0d11 |
|
|
|
|
|
1.11 |
Pendinginan- 2-tahap |
|
|
ONAN/ ONAF1/ ONAF2 |
|
|
|
|
|
1.12 |
Fungsi kumparan tersier (TV) |
|
|
Suplai tambahan |
|
|
|
|
|
1.13 |
Metode pembumian |
|
|
|
|
- HV |
|
|
Padat |
|
- LV kumparan |
|
|
Padat |
|
- TV berkelok |
|
|
- |
|
|
|
|
|
1.14 |
Tipe kumparan (kasar/tidak dinilai) |
|
|
|
|
- HV kumparan (Seri) |
|
|
Dinilai |
|
- LV kumparan (Umum) |
|
|
Dinilai |
|
- TV berkelok |
|
|
Tidak dinilai |
|
|
|
|
|
1.15 |
Tegangan tetapan kumparan (Ur) |
|
|
|
|
- HV |
KV |
|
400 |
|
- LV kumparan |
KV |
|
220 |
|
- TV berkelok |
KV |
|
11 |
|
Catatan*: Perkiraan; sesuai dengan preferensi pabrikan |
|
|
|
|
|
|
|
|
1.16 |
Tegangan tertinggi untuk peralatan (UM) |
|
|
|
|
- HV |
KV |
|
420 |
|
- LV kumparan |
KV |
|
245 |
|
- TV berkelok |
KV |
|
12 |
|
|
|
|
|
1.17 |
Impuls petir yang telah diukur saat menahan tegangan pada: |
|
|
|
|
- Terminal tegangan tinggi |
KV |
|
1425 |
|
- Terminal LV |
KV |
|
1050 |
|
- Terminal netral |
KV |
|
480 |
|
- TV berkelok |
|
|
75 |
|
|
|
|
|
1.18 |
Tegangan impuls sakelar tetapan |
|
|
|
|
- Terminal tegangan tinggi |
KV |
|
1050 |
|
- Terminal LV |
KV |
|
850 |
|
|
|
|
|
1.19 |
Frekuensi daya tetapan tahan terhadap tegangan pada posisi tegangan |
|
|
|
|
- Terminal HV (nilai desain) |
KV |
|
630 |
|
- nilai uji tegangan tinggi (ACLD U1) |
KV |
|
436 |
|
- nilai uji tegangan tinggi (pengukuran ACLD U2 PD) |
KV |
|
388 |
|
- Terminal LV (nilai desain) |
KV |
|
460 |
|
- Terminal netral |
KV |
|
70 |
|
- Terminal TV |
KV |
|
28 |
|
|
|
|
|
1.2 |
Daya tetapan pada kondisi lokasi (ONAF2 atau OFAF), HV & LV |
MVA |
|
200 |
|
|
|
|
|
1.21 |
Daya tetapan di kondisi lokasi (ONAN) |
MVA |
|
120 |
|
|
|
|
|
1.22 |
Daya terukur tersier di kondisi lokasi (Pendinginan penuh) |
MVA |
|
70 |
|
|
|
|
|
1.23 |
Kenaikan suhu maksimum pada daya tetapan di: |
|
|
|
|
- kumparan |
K |
|
55 |
Marikani |
||||
|
||||
|
- Titik kumparan panas |
K |
|
68 |
Marikani |
||||
|
||||
|
- Oli atas |
K |
|
50 |
Marikani |
||||
|
- Oli di saluran masuk cooler |
K |
|
Sekitar 22 |
|
- Oli di Saluran Keluar Cooler |
K |
|
Sekitar 50 |
|
- Inti |
K |
|
Sekitar 75 |
|
|
|
|
|
1.24 |
Temperatur kumparan karena durasi hubung singkat 2s pada beban tetapan |
|
|
|
|
- nilai hubung-singkat di sisi HV sebesar 31,5mm |
|
|
250 |
|
- nilai hubung-singkat sisi LV sebesar 31,5khA |
|
|
250 |
|
|
|
|
|
1.25 |
Kehilangan beban tanpa beban pada tegangan tetapan dan frekuensi tetapan |
KW |
|
45 |
|
|
|
|
|
1.26 |
Kehilangan beban pada 75, dan frekuensi tetapan: |
|
|
|
|
- kekuatan berperingkat ONAF2 atau OFAF dan sentuhan utama |
|
|
288 |
- Daya terukur ONF2 atau OFAF dan rasio tegangan maksimum |
|
|||
- Daya terukur ONF2 atau OFAF dan rasio tegangan minimum |
278 |
|||
- pada ketukan di ONAN yang dinilai secara langsung dan ketukan utama |
|
|||
|
350 |
|||
|
|
|||
|
105 |
|||
|
|
|
|
|
1.27 |
Kehilangan alat bantu total saat beban penuh |
KW |
|
Sekitar 10 |
|
|
|
|
|
1.28 |
Kerapatan arus maksimum pada daya tetapan: |
|
|
|
|
- HV |
A/mm2 |
|
Sekitar 2.0 |
|
- LV kumparan |
A/mm2 |
|
Sekitar 2.0 |
|
- TV berkelok |
A/mm2 |
|
Sekitar 3.6 |
|
- mengetuk |
A/mm2 |
|
Sekitar 3.6 |
|
|
|
|
|
1.29 |
Sirkuit pendek simetris melalui arus (durasi 2s) pada peringkat kerusakan sistem |
|
|
|
|
- Terminal HV (31,5kA) |
KA |
|
31.5 |
|
- terminal LV (31,5kA) |
|
|
31.5 |
|
|
|
|
|
1.3 |
Arus Magnefit (HV) |
|
|
|
|
- pada tegangan tetapan 90% |
A |
|
7x0,7 |
|
- pada tegangan tetapan 100% |
A |
|
Pendekatan9 |
|
- Tegangan tetapan Ar 110% |
A |
|
Pemberi Persetujuan x6,8 |
|
|
|
|
|
1.31 |
Kepadatan fluks maksimum pada besi pada voltase terukur, frekuensi daya dan ketukan utama pada: |
|
|
|
|
Tungkai - luka |
T |
|
7x1,7 |
|
- Limba tulang |
T |
|
7x1,7 |
|
- yoke |
T |
|
7x1,7 |
|
Perisai |
T |
|
7x1,7 |
1.32 |
Kepadatan fluks maksimum pada besi pada frekuensi daya, ketukan utama dan tegangan nominal 105% pada: |
|
|
|
|
Tungkai - luka |
T |
|
Sekitar 1.78 |
|
- Limba tulang |
T |
|
Sekitar 1.78 |
|
- yoke |
T |
|
Sekitar 1.78 |
|
Perisai |
T |
|
Sekitar 1.78 |
|
|
|
|
|
1.33 |
Ketik PF ketuk berubah |
|
Beban |
Beban |
|
|
|
|
|
1.34 |
Pembuat pengganti keran beban |
|
|
MR |
|
|
|
|
|
1.35 |
Tipe lambang pengganti keran beban |
|
|
M500-72.5/C-10193W |
|
|
|
|
|
1.36 |
Kumparan dengan diketuk |
|
HV |
HV |
|
|
|
|
|
1.37 |
Tipe variasi voltase fluks |
|
V. F.V.V |
V. F.V.V |
|
|
|
|
|
1.38 |
Mengetuk rentang |
|
-1 |
-1 |
|
|
|
|
|
1.39 |
Mengetuk langkah |
|
1.25% |
1.25% |
|
|
|
|
|
1.4 |
Jumlah langkah (posisi) |
|
16 (17) |
16 (17) |
|
|
|
|
|
1.41 |
Pengaturan pembungkus (Linier, kasar/Halus, Mundur) |
|
|
Bolak-balik |
|
|
|
|
|
1.42 |
Kontrol tegangan otomatis |
|
Ya |
Ya |
|
|
|
|
|
1.43 |
TEGANGAN IPEDO - LV pada 75 o C, frekuensi tetapan, dan peringkat penuh: |
|
|
|
|
- pada ketukan di kepala sekolah |
% |
>14% |
>14% |
|
- pada rasio tegangan maksimum |
% |
>14% |
>14% |
|
- pada rasio tegangan minimum |
% |
>14% |
>14% |
|
|
|
|
|
1.44 |
Impedansi HV-TV (ketukan prinsip) pada 70MVA |
% |
|
Sekitar 22.5 |
|
|
|
|
|
1.45 |
Hambatan kumparan dengan ketukan 75 dan ketukan Kepala pokok: |
|
|
|
|
- sisi tegangan tinggi |
Ω/fase |
|
Sekitar 0.53 |
|
Sisi LV |
Ω/fase |
|
Sekitar 0.58 |
|
- TV |
Ω/fase |
|
Sekitar 0.029 |
1.46 |
Koneksi terminal |
|
|
|
|
- Terminal tegangan tinggi |
|
Bushing luar ruangan |
Bushing luar ruangan |
|
- Terminal LV |
|
Bushing luar ruangan |
Bushing luar ruangan |
|
- Terminal netral |
|
Bushing luar ruangan |
Bushing luar ruangan |
|
- Terminal TV |
|
Bushing luar ruangan |
Bushing luar ruangan |
|
|
|
|
|
1.47 |
Jarak Creebrpage bushing (IEC class IV=31mm/kV) |
|
|
|
|
- terminal HV (420kV) |
mm |
13020 |
13020 |
|
- Terminal LV (245kV) |
mm |
7595 |
7595 |
|
- Terminal netral (36kV) |
mm |
≥900 |
≥900 |
|
- Terminal TV (12kV) |
mm |
372 |
372 |
|
|
|
|
|
1.48 |
Isolasi kotak kabel |
|
|
|
|
- Terminal tegangan tinggi |
|
TIDAK TERSEDIA |
TIDAK TERSEDIA |
|
- Terminal LV |
|
" |
TIDAK TERSEDIA |
|
- Terminal Netral |
|
" |
TIDAK TERSEDIA |
|
- Terminal Netral LV |
|
" |
TIDAK TERSEDIA |
|
- Tertiary |
|
" |
TIDAK TERSEDIA |
|
|
|
|
|
1.49 |
Mengisolasi link untuk tujuan pengujian |
|
|
|
|
- Terminal tegangan tinggi |
|
TIDAK TERSEDIA |
TIDAK TERSEDIA |
|
- Terminal LV |
|
" |
TIDAK TERSEDIA |
|
Terminal tersier |
|
" |
TIDAK TERSEDIA |
1.5 |
Transformer arus |
|
|
|
|
HV- TURREPUT bushing |
|
Rujuk ke Gambar Tender |
|
|
|
|
|
|
|
- jumlah Core |
|
|
3 |
|
- Arus utama tambahan tetapan |
|
|
500, 1000/500, 1000/500 |
|
- Rasio (TR= Rasio Belokan) |
|
|
|
|
•I core |
A |
|
500/1 |
|
•II Core |
A |
|
1000/500/1 |
|
•III core |
A |
|
1000/500/1 |
|
- Kelas |
|
|
|
|
•I core |
|
|
5P20 |
|
•II Core |
|
|
5P20 |
|
•III core |
|
|
5P20 |
|
- Tegangan titik lutut (Ek) |
|
|
|
|
•I core |
V |
|
1665 |
|
•II Core |
V |
|
3330/ 1665 |
|
• III core |
V |
|
3330/ 1665 |
|
- Arus menarik (IE) di |
|
|
|
|
•I core |
MA |
|
Akan memberikan nilai terukur |
|
•II Core |
MA |
|
Akan memberikan nilai terukur |
|
•III core |
MA |
|
Akan memberikan nilai terukur |
|
- Output peringkat (beban 25-100% beban tetapan) |
|
|
|
|
•I core |
VA |
|
30 |
|
•II Core |
VA |
|
30 |
|
•III core |
VA |
|
30 |
|
|
|
|
|
|
Garis LV (hanya koneksi AIS) |
|
|
|
|
|
|
|
|
|
- jumlah Core |
|
|
3 |
|
- Arus utama tambahan tetapan |
|
|
1500, 750,750 |
|
- Rasio (TR= Rasio Belokan) |
|
" |
1500/750/1; 750/1; 750/1 |
|
- Kelas |
|
" |
5P20 |
|
- Tegangan titik lutut (Ek) |
|
" |
4995, 2498, 2498 |
|
- Arus menarik (IE) di |
|
" |
Akan memberikan nilai terukur |
|
- Output peringkat (beban 25-100% beban tetapan) |
|
" |
30 |
|
|
|
|
|
|
Netral (HV REF) |
|
|
|
|
|
|
|
|
|
- jumlah Core |
|
|
1 |
|
- Arus utama tambahan tetapan |
|
|
500 |
|
- Rasio (TR= Rasio Belokan) |
|
|
|
|
* I core |
A |
|
500/1 |
|
- Kelas |
|
|
|
|
* I core |
|
|
5P20 |
|
- Tegangan titik lutut (Ek) |
|
|
|
|
* I core |
V |
|
1665 |
|
- Arus menarik (IE) di |
|
|
|
|
* I core |
MA |
|
Akan memberikan nilai terukur |
|
- Output peringkat (beban 25-100% beban tetapan) |
|
|
|
|
* I core |
VA |
|
15 |
|
|
|
|
|
|
Netral - berakhir |
|
|
|
|
|
|
|
|
|
- jumlah Core |
|
|
1 |
|
- Arus utama tambahan tetapan |
|
|
500 |
|
- Rasio (TR= Rasio Belokan) |
|
|
|
|
•I core |
A |
|
500/1 |
|
- Kelas |
|
|
|
|
•I core |
|
|
5P20 |
|
- Tegangan titik lutut (Ek) |
|
|
|
|
•I core |
V |
|
1665 |
|
- Arus menarik (IE) di |
|
|
|
|
•I core |
MA |
|
Akan memberikan nilai terukur |
|
- Output peringkat (beban 25-100% beban tetapan) |
|
|
|
|
•I core |
VA |
|
15 |
|
Semua PX kelas CTS memiliki arus sekunder terukur, TIDAK |
A |
|
1 |
|
|
|
|
|
|
Tersier |
|
|
|
|
- jumlah Core |
|
|
TIDAK TERSEDIA |
|
- Arus utama tambahan tetapan |
A |
|
TIDAK TERSEDIA |
|
- Rasio (TR= Rasio Belokan) |
|
|
|
|
* I core |
|
|
TIDAK TERSEDIA |
|
* II Core |
|
|
TIDAK TERSEDIA |
|
- Kelas |
|
|
|
|
* I core |
|
|
TIDAK TERSEDIA |
|
* II Core |
|
|
TIDAK TERSEDIA |
|
- Tegangan titik lutut (Ek) |
|
|
|
|
* I core |
V |
|
TIDAK TERSEDIA |
|
* II Core |
V |
|
TIDAK TERSEDIA |
|
- Arus menarik (IE) di |
|
|
|
|
* I core |
MA |
|
TIDAK TERSEDIA |
|
* II Core |
MA |
|
TIDAK TERSEDIA |
|
- Output peringkat (beban 25-100% beban tetapan) |
|
|
|
|
* I core |
VA |
|
TIDAK TERSEDIA |
|
* II Core |
VA |
|
TIDAK TERSEDIA |
|
|
|
|
|
1.51 |
Jumlah cooler per transformer |
|
|
Sekitar 10 |
|
|
|
|
|
1.52 |
Jumlah cooler yang tahan berdiri |
|
|
TIDAK TERSEDIA |
|
|
|
|
|
1.53 |
Jumlah kipas berdiri |
|
|
1 |
|
|
|
|
|
1.54 |
Peringkat setiap cooler |
KW |
|
0.75 |
|
|
|
|
|
1.55 |
Oli |
|
|
|
|
- produsen |
|
|
Dijadikan NITRO |
|
- ketik penetapan |
|
|
GBN1 |
|
- Standar |
|
IEC 60296 |
IEC 60296 |
|
- Titik flash minimum |
|
|
140 |
|
- Viskositas |
|
|
|
|
* di 20 derajat celcius |
mm2/dtk |
|
IEC 60296 |
|
* di 50 derajat |
mm2/dtk |
|
IEC 60296 |
|
* di 80 |
mm2/dtk |
|
IEC 60296 |
|
- kekuatan dielektrik maksimum selama 1 mnt |
KV |
|
70 |
|
- faktor dielektrik |
|
|
0.005 |
|
- keasaman (nilai penetralan) |
MgKOH/g |
|
0.01 |
|
|
|
|
|
1.56 |
Sistem penahanan oli |
|
Kantung-udara |
Kantung-udara |
1.57 |
Tipe dan pengaturan kumparan: |
|
|
|
|
- HV |
|
|
Cakram |
|
- LV kumparan |
|
|
Cakram |
|
- TV berkelok |
|
|
Cakram |
|
- mengatur |
|
|
Cakram |
|
Pengaturan kumparan (yaitu Inti/TV/ LV/ HV/ Tap) |
|
|
Core/TV/Tap/ LV/ HV/ |
1.58 |
Materi konduktor (mis. Tembaga, tembaga diperkeras kerja, dsb.) |
|
|
|
|
- kumparan tegangan |
|
|
Bekerja dengan tembaga yang diperkeras |
|
- kumparan LV |
|
|
Bekerja dengan tembaga yang diperkeras |
|
- kumparan TV |
|
|
Bekerja dengan tembaga yang diperkeras |
|
- Mengatur kumparan |
|
|
Bekerja dengan tembaga yang diperkeras |
|
- menyambungkan kabel dari kumparan ke pengganti keran |
|
|
Bekerja dengan tembaga yang diperkeras |
1.59 |
Isolasi konduktor: |
|
|
|
|
- kumparan tegangan |
|
|
Kertas |
|
- kumparan LV |
|
|
Kertas |
|
- kumparan TV |
|
|
Kertas |
|
- Mengatur kumparan |
|
|
Kertas |
|
- menyambungkan kabel dari kumparan ke pengganti keran |
|
|
Kertas |
1.6 |
Konstanta waktu termal terhitung |
|
|
|
|
- NYALA pendingin |
min |
|
Oli:210 kumparan:10 |
|
- Pendinginan penuh |
min |
|
Oli:90 kumparan:7 |
|
|
|
|
|
1.61 |
Sirkulasi Oli (yaitu, diarahkan/ diarahkan secara alami/sebagian) |
|
|
|
|
Ke kumparan: |
|
|
|
|
- kumparan HV (Seri) |
|
|
Alami |
|
- kumparan LV (Umum) |
|
|
Alami |
|
- Mengatur kumparan |
|
|
Alami |
|
- kumparan TV |
|
|
Alami |
|
Melalui kumparan: |
|
|
|
|
- kumparan HV (Seri) |
|
|
Buka |
|
- kumparan LV (Umum) |
|
|
Buka |
|
- Mengatur kumparan |
|
|
Alami |
|
- kumparan TV |
|
|
Buka |
1.62 |
Konstruksi inti: |
|
|
|
|
- menjilid/ berpita/ tungkai |
|
|
Tungkai menjilid |
|
- yoke terbungkus/berpita berbaut |
|
|
Yoke |
|
- menumpuk / merekbanding material |
|
|
Pembalut untuk epoksi |
|
- jumlah Limba |
|
|
3 |
|
– jumlah luka tungkai |
|
|
3 |
|
- Tipe sambungan dalam inti magnetik (90% Butt, overlap, Mitre, dll.) |
|
|
Tumpang tindih |
|
- Tipe baja inti |
|
|
23RK85 |
|
– penurunan khusus baja inti pada 1.5 tesla |
W/kg |
|
Sekitar 0.7 |
|
|
|
|
|
1.63 |
Ketebalan tangki transformer |
|
|
|
|
Bagian - |
mm |
|
10 |
|
Bawah |
mm |
|
10 |
|
Atas |
mm |
|
25 |
|
|
|
|
|
1.64 |
Material tangki transformer |
|
|
Q235 |
|
|
|
|
|
1.65 |
Ketebalan pelat radiator |
mm |
|
1 |
|
|
|
|
|
1.66 |
Volume konservatif total |
Liter |
|
Sekitar 4000 |
|
|
|
|
|
1.67 |
Volume konservatif minimal antara level tertinggi dan terendah Persentase total oli dingin pada volume transformer 15 derajat |
|
7.50% |
7.50% |
|
|
|
|
|
1.68 |
Penambahan volumetrik minyak dari celcius sampai 90celcius |
m3 |
|
Sekitar 5.7 |
|
|
|
|
|
1.69 |
Peningkatan tekanan di dalam tangki karena ekspansi oli |
|
|
TIDAK TERSEDIA |
|
|
|
|
|
1.7 |
Massa trafo |
|
|
|
|
- Core dan coil |
kg |
|
Sekitar 93000 |
|
- Oli pengecualian massa total |
kg |
|
Sekitar 140000 |
|
- Massa oli * dalam tangki |
kg |
|
Sekitar 61000 |
|
* di radiator |
kg |
|
Sekitar 2500 |
|
* total |
kg |
|
Sekitar 81000 |
|
- Total massal |
kg |
|
Sekitar 221000 |
|
|
|
|
|
1.71 |
Massa transformer yang diatur untuk pengangkutan (bagian terberat) |
kg |
|
Sekitar 120000 |
|
|
|
|
|
1.72 |
Dimensi transformer diatur untuk pengangkutan |
|
|
|
|
- Tinggi |
m |
|
|
|
- Lebar |
m |
|
|
|
- Panjang |
m |
|
|
|
|
|
|
|
1.73 |
Mengisi medium tangki transformer untuk pengiriman |
|
|
Udara kering |
|
|
|
|
|
1.74 |
Tingkat tekanan suara maksimum (NEMA TR1- 5dB(A)) |
DB(A) |
82 |
82 |
1.75 |
Pembuluh darah Conservator, radiator, kisi-kisi kipas, kotak kontrol, bilik, dan perlindungan antikorrom |
|
Galvanisasi panas dan Cat |
Galvanisasi panas dan Cat |
|
|
|
|
|
1.76 |
Perlindungan antikorrsion tangki |
|
|
Dicat |
|
|
|
|
|
1.77 |
Tegangan suplai untuk alat bantu transformer |
V |
415/ 240 AC |
415/ 240 AC |
|
|
|
|
|
1.78 |
Tegangan Kontrol/Perlindungan |
V |
110 DC |
110 DC |
|
|
|
|
|
1.79 |
Jaminan kualitas dari produsen |
|
Ya |
Ya |
|
- sesuai dengan ISO 9000, 9001, 9002, 9003 dan 9004 |
|
validitas |
validitas |
|
|
|
|
|
1.8 |
Ketik sertifikat uji yang akan dikeluarkan oleh: |
|
|
|
|
- Laboratorium independen atau sertifikat uji jenis yang disaksikan secara independen |
|
Ya |
Ya |
|
|
|
|
|
1.81 |
Pengujian khusus yang akan dilakukan: |
|
|
|
|
Sebagai Type test= T |
|
|
|
|
Sebagai tes rutin= R |
|
|
|
|
- dielektrik test- membagi impuls petir gelombang |
|
Ya (R) |
Ya (R) |
|
- uji dielektrik- durasi pendek AC (ACSD) |
|
Tidak |
Tidak |
|
- Pengukuran impedansi urutan nol |
|
TIDAK TERSEDIA |
TIDAK TERSEDIA |
|
Penentuan tingkat suara |
|
Ya (T) |
Ya (T) |
|
- Pengukuran harmonik arus tanpa beban |
|
Ya (R) |
Ya (R) |
|
- Pengukuran daya motor kipas & pompa oli |
|
Ya (T) |
Ya (T) |
|
- Penentuan kapasitansi, kumparan ke bumi dan antar kumparan |
|
Ya (R) |
Ya (R) |
|
- Pengukuran resistan isolasi ke tanah dan sudut yang hilang kapasitas sistem isolasi |
|
Ya (R) |
Ya (R) |
|
- Pengujian getaran |
|
Tidak |
Tidak |
Pemasok dengan izin usaha terverifikasi