Tipe: | Power Source Arraster |
---|---|
Struktur: | Zinc Oksida Flap |
Instalasi: | Arrester Paralel |
Aplikasi: | Sistem AC/DC |
Ukuran: | Kecil |
Tegangan Operasi: | Tegangan Rendah |
Pemasok dengan izin usaha terverifikasi
This AC surge protective device is applied low voltage standard IEC/EN 61643-11 to protect against AC power line system and other equipment from over voltage and instantaneous over voltage damage. It has advantages of large discharge current, fast respond time and low residual voltage.
Model
|
LY1-D20
|
Maximum Continuous Operating Voltage Uc
|
275V AC
|
SPD Type
|
Type 2+3/Class II+III |
Nominal Discharge Current (8/20µs)
|
10kA
|
Maximum Discharge Current(8/20µs)
|
20kA
|
Voltage Protection Level Up
|
≤1.5kV
|
Response Time tA
|
≤25ns
|
Indication Method
|
Visible window,Green=normal, Red=defect
|
Method of Installation
|
35mm Din Rail
|
Material of shell
|
PBT firproof
|
Protection level of outer Shell
|
IP20
|
Working temperature
|
-40 -+70ºC
|
Test standard
|
IEC/EN 61643-31
|
Poles
|
1P/2P/3P/4P/1P+N-PE/3P+N-PE
|
Pemasok dengan izin usaha terverifikasi