Theory: | Electromagnetic Relay |
---|---|
Usage: | Household Appliances Relay, Communication Relay |
Phase: | 3 |
Electricity Type: | Ac |
Number of Pole: | 3 |
Action Principle: | Electronic Type |
Pemasok dengan izin usaha terverifikasi
Contoh |
Tegangan-lebih |
Kurang tegangan |
Unblance |
Urutan fase |
Kegagalan fase | Atur ulang |
Uji |
Proteksi PTC | Perlindungan beban | |||
ZHRV1 |
Rentang Pengaturan | Rentang Penundaan | Rentang Pengaturan | Rentang Penundaan | Rentang Pengaturan | Rentang Penundaan | ||||||
01 | 1.05...1.30 | 0,1s...10dtk | - | - | - | - | - | + | - | - | - | - |
02 | - | - | 0.70...0.95 | 0,1s...10dtk | - | - | - | + | - | - | - | - |
03 | 1.05...1.30 | 0,1s...10dtk | 0.70...0.95 | 0,1s...10dtk | - | - | - | + | - | - | ○ | ○ |
04 | 1.05...1.30 | 0,1s...10dtk | 0.70...0.95 | 0,1s...10dtk | - | - | + | + | - | - | ○ | ○ |
05 | 1.05...1.30 | 0,1s...10dtk | 0.70...0.95 | 0,1s...10dtk | 8% | 2s | - | + | - | - | ○ | ○ |
06 | 1.05...1.30 | 0,1s...10dtk | 0.70...0.95 | 0,1s...10dtk | 8% | 2s | + | + | - | - | ○ | ○ |
07 | 1.05...1.30 | 0,1s...10dtk | 0.70...0.95 | 0,1s...10dtk | 5%...15% | 0,1s...10dtk | - | + | - | - | ○ | ○ |
08 | 1.05...1.30 | 0,1s...10dtk | 0.70...0.95 | 0,1s...10dtk | 5%...15% | 0,1s...10dtk | + | + | - | - | ○ | ○ |
09 | 1.05...1.30 | 2s | 0.70...0.95 | 2s | 8% | 2s | - | + | - | - | ○ | ○ |
10 | 1.05...1.30 | 2s | 0.70...0.95 | 2s | 8% | 2s | + | + | ○ | ○ | ○ | ○ |
11 | 1.15 | 2s | 0.85 | 2s | 5%...15% | 0,1s...10dtk | - | + | ○ | ○ | ○ | ○ |
12 | 1.15 | 2s | 0.85 | 2s | 5%...15% | 0,1s...10dtk | + | + | ○ | ○ | ○ | ○ |
13 | 1.15 | 2s | 0.85 | 2s | 8% | 2s | - | + | ○ | ○ | ○ | ○ |
14 | 1.15 | 2s | 0.85 | 2s | 8% | 2s | + | + | ○ | ○ | ○ | ○ |
15 | 1.15 | 2s | 0.85 | 2s | - | - | - | + | ○ | ○ | ○ | ○ |
16 | 1.15 | 2s | 0.85 | 2s | - | - | + | + | - | - | - | - |
17 | - | - | - | - | 5%...15% | 0,1s...10dtk | + | + | - | - | - | - |
18 | - | - | - | - | - | - | + | + | - | - | - | - |
19 | - | - | - | - | 8% | 2s | + | + | - | - | - | - |
Tegangan suplai tetapan | AC220V, AC230, AC240V,AC380V,AC400V,AC415V |
Frekuensi catu daya tetapan | 50Hz/60Hz |
Rentang ambang batas tegangan berlebih | (1.05 Masuk 1.30)*Ue |
Rentang ambang di bawah tegangan | (0.70 Masuk 0.95)*Ue |
Rentang ambang batas tak seimbang | 5%-15% |
Rentang penundaan tindakan | 0,1s-10s |
Fase rusak dan urutan fase | ≤1s |
Kesalahan pengukuran tegangan | ≤1%(seluruh rentang pengaturan) |
Kesalahan penundaan | ±10%+0,1 |
Akurasi pengaturan kenop | ±1% nilai skala |
Tegangan isolasi tetapan | 415V |
Kapasitas konfigurasi kontak(A) | 10 A |
Kelas IP | IP20 |
Kelas polusi | 3 |
Masa pakai listrik | 105 |
Kehidupan manusia yang lMekanik | 106 |
Ketinggian | ≤2000 m |
Kelembapan relatif yang diperbolehkan | ≤50%(40)(tanpa kondensasi) |
Gunakan kategori | AC-15 |
Tipe pelindung hubung-singkat | RT36-00 5A |
Kapasitas kontak | Ue/le:240V/1,5A,415V/0,95A |
Tipe output | 1C/O. |
Standar rel DIN | Lebar 35mm(IEC/EN60715) |
Pemasok dengan izin usaha terverifikasi